MTU Gas Power Plant

Description

General Introduction
Great performance. Great flexibility. Reliability, Profitability.MTU provide continuous power. The systems are flexible in size and location, and readily available to meet urgent power needs. We offer support in all project phases from requirement analyses to defining the best solution, implementation, hand-over, spare parts and service support and individual, full maintenance contracts. Besides we also can offer combined heat and power (CHP) solutions to generator power. Our products combine the highest performance with the lowest emissions in the 120 kW – 2.145 kW electrical power range.

Features
Gas Engine Series 400
   Output range from 120 to 420 kW
> Continuous development and optimization for more than 35 years
> Meeting common industrial quality standards
> Highest overall efficiency in its power range (up to 91.9%)
> Sophisticated compact design
> Factory tested with comprehensive performance evaluation
> Cylinder-selective knock control

Gas Engine Series 4000
   Output range from 854 to 2145kW
> Proven mechanical components
> Very high power density
> Cylinder-selective knocks control
> Factory tested with comprehensive performance evaluation
> Single cylinder heads with four-valve technology

Your benefits:
> Engine technology adapted to the application
> Optimal integration of our engines into the drive concept
> Versatile and modular engine control
> Compact design and low weight
> Maintenance friendliness
> Reliability
> First-class application engineering
> Worldwide service and parts supply

Parameter

Natural gas genset with heat extraction from jacket water and exhaust gas (Cogeneration Module 90°/70 ℃ )
Engine type Electrical  Power (Kw) Bore/stroke (mm) Displacement (L) Thermal  Output (Kw) Electrical  Efficiency
 (%)
Total  Efficiency
(%)
Dimension (L/H)
ME 3066 D3 119 130/155mm 12.36 198 34.5 91.9 3650×960×1875
ME 3066 L3 182 130/155mm 12.36 280 35 88.7 3520×1800×2060
ME 3066 L3 201 130/155mm 12.36 275 34.9 82.6 3520×1800×2060
ME 3066 Z5 220 130/155mm 12.36 262 39 85.5 3880×1870×2140
ME 3042 D3 232 130/142mm 22.56 358 35.4 91.8 3550×1810×2220
ME 3042 L3 357 130/142mm 22.56 529 36.2 89.8 3700×1810×2270
ME 3042 Z3 386 130/142mm 22.56 541 36.4 87.4 3700×1810×2270
ME 3042 Z6 390 130/142mm 22.56 474 39.2 86.8 3850×1870×2250
ME 3042 Z6 420 130/142mm 22.56 504 39.5 86.8 3850×1870×2250
*NOx < 500 mg/mn3    **λ =1 with 3-Way-Catalyst, NOx < 250 mg/ mn3
1) cosψ = 1,0 in accordance with VDE 0530 REM                      2) From jacket water, tolerance 8%
3) From jacket water and exhaust gas, tolerance 8%                     4) Data only provided for external gas mixture cooler
5) Performance data in accordance with ISO 3046/I-1991, tolerance 5%     6) Referenced methane number
Natural gas genset with heat extraction from jacket water(heat recovery unit included in delivery)and exhaust gas (exhaust gas heat exchanger loose supply )
Engine type Electrical  Power (Kw) Bore/stroke (mm) Displacement (L) Thermal  Output (Kw) Electrical  Efficiency
 (%)
Total  Efficiency
(%)
Dimension (L/H)
AE8V4000L33 776 170/210mm 38.16 823 42.4 87.3 5750×1990×2400
AE12V4000L33 1169 170/210mm 57.24 1228 42.8 87.8 6300×1850×2400
AE16V4000L33 1560 170/210mm 76.32 1662 42.8 88.3 7100×1850×2400
AE20V4000L33 1948 170/210mm 95.4 2098 42.7 88.7 7600×1850×2400
AE8V4000L33 776 170/210mm 38.16 823 42.4 87.3 5750×1990×2400
* NOx < 500 mg/mn3 (NOx < 250 mg/mn3 available)
1) Rated power at nominal voltage, power factor = 1 and nominal frequency   2) From jacket water, tolerance 8%
3) From jacket water and exhaust gas (120°C), tolerance 8%    4) Performance data in accordance with ISO 3046, tolerance 5%
5) Referenced methane number                           6) Dimensions without exhaust gas heat exchanger